| Item Code: | FST 951R |
|---|---|
| Sensitivity: | UL Applications: 0.5% to 4.0% per foot obscuration. ULC is 0.5% to 3.5% |
| Size: | 2.0″ (5.3 cm) high; base determines diameter – B300-6: 6.1″ (15.6 cm) diameter – B501: 4″ (10.2 cm) diameter |
| Shipping weight: | 3.4 oz. (95 g) |
| Operating temperature range: | • FST-951, FST-951R Series: –4°F to 100°F (–20°C to 38°C) • FST-951H Series: –4°F to 150°F (–20°C to 66°C) |
| Detector spacing: | UL approved for 50 ft. (15.24 m) center-to-center, FM approved for 25 x 25 ft. (7.62 x 7.62 m) spacing |
| Relative humidity: | 10% – 93% non-condensing |
| Thermal ratings: | fixed-temperature set point 135°F (57°C), rate-ofrise detection 15°F (8.3°C) per minute, high temperature heat 190°F (88°C) |
| Mounting: | B300-6(A) flanged base, included |
| Voltage range: | 15 – 32 volts DC peak |
| Standby current (max. avg.): | 200µA @ 24 VDC (one communication every 5 seconds with LED enabled) |
| Max current: | 4.5 mA @ 24 VDC (“ON”) |