NFS2-3030
Intelligent Fire Alarm Control Panel
Brand:
Brochure Link: Download
System Capacity
| Item Code: | NFS2-3030 |
|---|---|
| Intelligent Signaling Line Circuits: | 1 expandable to 10 |
| Intelligent detectors: | 159 per loop |
| Addressable monitor/control modules: | 159 per loop |
| Programmable software zones: | over 2000 |
| ACS annunciators per CPU2-3030: | 32 address x 64 or 96 points |
| Primary Input Power: | – AMPS-24: 110-120 VAC, 50/60 Hz, 4.5 A maximum. – AMPS-24E: 240 VAC, 50/60 Hz, 2.25 A maximum. |
|---|---|
| DC Output: | – Main 24 VDC: Up to 5.0 A – Aux 24 VDC: Up to 5.0 A – 5 VDC: Up to 0.15 A. |
| Current draw (Standby/Alarm): | – CPU2-3030D board: 0.340 A. – CPU2-3030ND board: 0.120 A. – LCM-320: 0.130 A. – LEM-320: 0.100 A. – AMPS-24(E)*: 0.13 A. (Draws power from secondary power source only.) |
| Battery charger range: | 7 AH – 200 AH. Use separate cabinet for batteries over 26 AH. |
| Float Rate: | 27.6 V |
| Shipping Weight: | • CPU2-3030D: 5.95 lb (2.70 kg). • CPU2-3030ND: 2.90 lb (1.32 kg). |
| NFPA requirements for operation: | 0 – 49°C/32 – 120°F |
| Relative Humidity 93% ± 2% RH (noncondensing): |
32°C ± 2°C (90°F ± 3°F) |