NFS2-640(E)
Intelligent Fire Alarm Control Panel
Brand:
Brochure Link: Download
System Capacity
| Item Code: | NFS2-640(E) |
|---|---|
| Intelligent Signaling Line Circuits: | 1 expandable to 2 |
| Intelligent detectors: | 159 per loop |
| Addressable monitor/control modules: | 159 per loop |
| Programmable software zones: | 99 |
| Special programming zones: | 14 |
| LCD annunciators per CPU2-640/-640E and NCA-2 (observe power): | 32 |
| ACS annunciators per CPU2-640/-640E: | 32 addresses x 64 points |
| ACS annunciators per NCA-2: | 32 addresses x 64 or 96 points |
Electrical Specifications
| Primary Input Power: | – CPU2-640 board: 120 VAC, 50/60 Hz, 5.0 A. – CPU2-640E board: 220/240 VAC, 50/60 Hz, 2.5 A. |
|---|---|
| Current draw (standby/alarm): | – CPU2-640(E) board: 0.250 A. Add 0.035 A for each NAC in use. – KDM-R2: 0.100 A. – LEM-320: 0.100 A |
| Total output 24 V power: | 6.0 A in alarm NOTE: The power supply has a total of 6.0 A. of available power. This is shared by all internal circuits. See Installation Manual for a complete current draw calculation sheet. |
| Standard notification circuits (4): | 1.5 A each |
| Resettable regulated 24V power: | 1.25 A |
| Two non-resettable regulated 24V power outputs: | – 1.25 A – 0.50 A |
| Non-resettable 5V power: | 0.15 A |
| Battery charger range: | 18 AH – 200 AH. Use separate cabinet for batteries over 26 AH. |
| Float rate: | 27.6 V |
| Shipping Weight: | • CPU2-640/-640: 14.3 lb (6.49 kg) • CPU2-640/-640E: 14.55 lb (6.60 kg) |
| NFPA requirements for operation: | 0 – 49°C/32 – 120°F |
| Relative Humidity 93% ± 2% RH (noncondensing): | 32°C ± 2°C (90°F ± 3°F) |