Red5 Access System
Red5-MODULE-1DOOR: Access Module
Brand:
Brochure Link: Download
| Inputs: | 1 Wiegand input for credential reader data (reader, keypad, biometric device, etc.) 1 input for request-to-exit switch 1 input for door contact |
|---|---|
| Outputs: | 1 LED open collector for credential reader 12 VDC, -25 mA max 1 binary outputs for credential reader power 12 VDC, 300 mA 2 binary outputs for powering requestto-exit or door accessories 1 24 VDC, 450 mA 1 12 VDC, 100 mA 2 binary outputs for door lock or door accesories 1 24 VDC, 450 mA 1 12 VDC, 475 mA |
| Universal Point (Input or Output): | 1 input (16-bit), supporting: 0–5 VDC 0–10 VDC 10 kΩ thermistor Dry contact (using 10 kΩ thermistor software setting) 4–20 mA (using external 250 Ω resistor on 0–5 V setting) 1 output (12-bit), supporting: 0–10 V @ 20 mA max |
| Connectors: | Removable screw-type terminal connectors |
| Wiring Class: | Class 2 / SELV |
| Power: | 24 VDC, 1.5 A (36 W max) |
| Ambient: | −30°C to 55°C (−22°F to 131°F) 10% to 95% RH (non-condensing) |
| Dimensions: | 57 × 107 × 58 mm (2.2 × 4.2 × 2.3 in.) |
| Weight: | 102 g (0.22 lb) |
| Compliance: | CE FCC |
| Listings: | C-UL Listed UL 916 Listed |