XP6-R
Six Relay Control Module
Brand:
Brochure Link: Download
| Item Code: | XP6-R |
|---|---|
| Standby current: | 1.45 mA (SLC current draw with all addresses used; if some addresses are disabled, the standby current decreases) |
| Alarm current: | 32 mA (assumes all six relays have been switched once and all six LEDs solid ON) |
| Temperature range: | 32°F to 120°F (0°C to 49°C) |
| Humidity: | 10% to 93% non-condensing |
| Dimensions: | 6.8″ (17.27 cm) high x 5.8″ (14.73 cm) wide x 1.0″ (2.54 cm) deep |
| Shipping weight: | 1.1 lb. (0.5 kg) including packaging |
| Mounting options: | CHS-6 chassis, BB-25 cabinet, BB-XP cabinet, CAB-3 Series (see DN-3549) cabinet, CAB-4 Series (see DN-6857) cabinet, or EQ Series (see DN-60229) cabinet |
| Wire gauge: | 12 AWG (3.25 mm²) to 18 AWG (0.9 mm²) |
| Maximum SLC wiring resistance: | 40 or 50 ohms, panel dependent |
| Relay current: | 30 mA/relay pulse (15.6 ms pulse duration), pulse under panel control |
| Relay contact ratings: | 30 VDC; 70.7 VAC |
| Current ratings: | • 3.0 A @ 30 VDC maximum, resistive, non-coded. • 2.0 A @ 30 VDC maximum, resistive, coded. • 1.0 A @ 30 VDC maximum, inductive (L/R = 2 ms), coded. • 0.5 A @ 30 VDC maximum, inductive (L/R = 5 ms), coded. • 0.9 A @ 110 VDC maximum, resistive, non-coded. • 0.9 A @ 125 VAC maximum, resistive, non-coded. • 0.7 A @ 70.7 VAC maximum, inductive (PF = 0.35), noncoded. • 0.3 A @ 125 VAC maximum, inductive (PF = 0.35), noncoded. • 1.5 A @25 VAC maximum, inductive (PF = 0.35), noncoded. • 2.0 A @25 VAC maximum, inductive (PF = 0.35), noncoded. |